PDLUX PD-LED2040-D
When using LED Emergency Lighting Microwave Induction Lamp, please adjust the sensitivity (detection range) to an appropriate value but the maximum to avoid the abnormal reaction caused by the easy detection of the wrong motion by the blowing leaves & curtains, small animals or the interference of power grid & electrical equipment. All the above mentioned will lead to the error reaction. When the product does not work normally, please try to lower the sensitivity appropriately, and then test it.
PD-LED2040-D Microwave Sensor Light Instruction
![]() |
Summary This is a newly designed intelligent ceiling mount microwave sensor LED light, with the extra function of power supply in emergency. The lighting is auto-managed by AC direct power or battery backup, that is, when power failure, the battery backup will be responsible for the power supply of 3.5 watt.The battery backup can continuously supply power for more than 3 hours or even more in the sensor energy-saving mode. It is widely applied in the corridor, washing room, elevator lobby etc. This product is designed with two configurations: one is the sensor lamp with the function of supplying power in emergency and the other one is the intelligent sensor lamp without the emergency function. You can make purchase according to the practical need. But in most cases, it is necessary and wise to choose the former one, for that the occasional power outage will cause trouble, or even danger. |
![]() |
Use high quality PC lampshade.Strengthen the flexible refraction of light.And its function of anti-ultraviolet makes the shade not easy to turn yellow and be broken. |
![]() |
LED lamp consumes power 80% less than incandescent lamp and 50% less than fluorescent lamp. |
Name of each part
Specifications
Power source: 100-240V/AC, 50/60Hz Rated LED: 15W Max.(AC) 3.5W Max.(DC) Charging power: <4W Max.(light off & light on) Slaving capacity:1A Max(100-240V/AC) HF system: 5.8GHz Battery: 7.4V / 1500mAH lithium battery Continuous illumination time: ≥180min Transmission power: <0.2mW |
Time setting: 10sec to 12min (adjustable) Detection range: 2-10m (radii.) (adjustable) Light-control: 10-2000LUX(adjustable) Detection angle: 360° Power factor:>0.9 Installation height: 2.5-3.5m (ceiling mount) Standby power:<0.5W LED quantity: 72PCS Working temperature: -20~+55℃ |
Information sensor
Function of LED Emergency Lighting Microwave Induction Lamp
Setting manner :potentiometer
LED Emergency Lighting Microwave Induction Lamp may take times to adjust values before they satisfy your need.
(1)Detection range setting (sensitivity)
![]() |
Detection range is the term used to describe the radii of the more or less circular detection zone produced on the ground after mounting the sensor light at a height of 2.5m, turn the reach control fully anticlockwise to select minimum reach (approx.2m radii), and fully clockwise to select maximum reach (approx. 10m radii). |
(2)Time setting
![]() |
The light can be set to stay ON for any period of time between approx. 10sec(turn fully anti-clockwise) and a maximum of 12min(turn fully clockwise). Any movement detected before this time elapse will re-start the timer. It is recommended to select the shortest time for adjusting the detection zone and for performing the walk test. |
(3)Light-control setting
![]() |
The chosen light response threshold can be infinitely from approx.10- 2000LUX. Turn it fully anti-clockwise to select dusk- to-dawn operation at about 10 lux. Turn it fully clockwise to select daylight operation at about 2000lux. The knob must be turned fully clockwise when adjusting the detection zone and performing the walk test in daylight. |
![]() |
It can be defined in the range of 0%~30%. When the ambient light is less than 70 lux, the system starts dimming mode. If there is no signal detected during the delay time, it will enter the percentage lighting. Once signal detected, it recovers to 100% lighting. It will auto exit dimming mode, when the ambient light is over 100 lux. The dimming mode works digitally and independently. |
Battery Switch This switch is to control the battery connection. To avoid power-consumption in transit or in storage, we preset the switch to OFF, that is, the battery is not connected. Before installation, you should set the switch to ON to make sure that the battery is well connected to achieve the power-supply in emergency. |
![]() |
Installation |
Connection-wire diagram |
Fault and the solution
Fault | Failure cause | Solution |
Does not work with the load | Light-illumination set incorrectly, the load is broken | Adjust the setting of the load |
The power is off | Change the load | |
There is a continuous signal in the region of the detection | Turn the power on | |
Work all the time with the load | The sensor have not been installed correctly | Check the settings of the detection area |
When there is no a moving signal work with the load | Sensors failed to pack good cause its cannot reliably detect signal | Re-install the outer covering |
Moving signal is detected by the sensor (movement behind the wall, the movement of small objects, etc.) | Check the settings of the detection area | |
When there is a moving signal work with the load | The moving body is too fast or the detection area is too small | Check the settings of the detection area |
1.The LEDS in serial can function when all the seals installed in place.
2.Please don’t remove or connect with other lamp when powered on.
3.When the LEDS in serial are damaged ,you need experienced technician to repair using the same rating LEDS.
●Please confirm with prefessional installation.
●For safety purposes, please cut off power before installation and removal operations.